Parameter
Value
Input delay (0->1 or 1->0)
Typ. 8 ms, configurable from 0.1 to 32 ms
Input signal voltage
24 V DC
Signal 0
-3 V...+5 V
Undefined signal
> +5 V...< +15 V
Signal 1
+15 V...+30 V
Ripple with signal 0
Within -3 V...+5 V
Ripple with signal 1
15 V...+30 V
Input current per channel
Input v24 V
Typ. 5 mA
Input v5 V
> 1 mA
Input v15 V
> 5 mA
Input v30 V
< 8 mA
Max. cable length
Shielded
1000 m
Unshielded
600 m
Technical data of the relay outputs
Parameter
Value
Number of channels per module
8 relay outputs
Distribution of channels into groups
8 groups of 1 channel each
Connection of the channel R0
Terminal 2.0 (common), 3.0 (NO) and 4.0 (NC)
Connection of the channel R1
Terminal 2.1 (common), 3.1 (NO) and 4.1 (NC)
Connection of the channel R6
Terminal 2.6 (common), 3.6 (NO) and 4.6 (NC)
Connection of the channel R7
Terminal 2.7 (common), 3.7 (NO) and 4.7 (NC)
Galvanic isolation
Between the channels and from the rest of the module
Indication of the output signals
One yellow LED per channel, the LED is ON when the
relay coil is energized
Monitoring point of output indicator
LED is controlled by process CPU
Way of operation
Non-latching type
Output delay (0->1 or 1->0)
On request
Relay power supply
By UP process supply voltage
Relay outputs
Output short circuit protection
Should be provided externally with a fuse or circuit
breaker
Rated protection fuse
6 A gL/gG per channel
Min. switching current
10 mA
Output switching capacity
Resistive load, max.
3 A; 3 A (230 V AC), 2 A (24 V DC)
Inductive load, max.
1.5 A; 1.5 A (230 V AC), 1.5 A (24 V DC)
Lamp load
60 W (230 V AC), 10 W (24 V DC)
Device specifications
I/O modules > Digital I/O modules
2022/01/31
3ADR010278, 3, en_US
337