Parameterization
The arrangement of the parameter data is performed with Automation Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Name
Value
Internal
value
Internal
value,
Type
Default
Min.
Max.
EDS Slot
Index
Module ID Intern
6505
1
)
WORD
0x1969
0
65535
xx01
Ignore
module
No
Yes
0
1
BYTE
No
0x00
Parameter
length
Intern
4
BYTE
0
0
255
xx02
2
)
Check
Supply
Off
On
0
1
BYTE
On
0x01
Analog
Data
Format
Default
0
BYTE
Default
0x00
255
1
) with CS31 and addresses less than 70, the value is increased by 1
2
) Value is hexadecimal: HighByte is slot (xx: 0...7), LowByte is index (1...n)
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
0x07
0x6A, 0x19, 0x04, \
0x01, 0x00, \
0x00, 0x00;
Input channel (2x)
Name
Value
Internal
value
Internal
value, Type
Default
Min.
Max.
Channel
configura-
tion
see table
2
) see table
2
) BYTE
0
0x00 see
table
3
)
0
65535
Table 76: Channel configuration
2
)
Internal value
Operating modes for the analog inputs,
individually configurable
0
Not used (default)
3
)
8
2-wire Pt100 -50 °C...+400 °C
9
3-wire Pt100 -50 °C...+400 °C
16
2-wire Pt1000, -50 °C...+400 °C
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US