Parameter
Value
Output current
Rated current per channel (max.)
2.0 A (24 V DC resistance and general use,
100 V AC...240 V AC, resistance, general
use and pilot duty)
Rated current per group (max.)
6 A
Rated current (all channels together, max.)
12 A
Demagnetization when inductive loads are
switched off
External demagnetization measures must be
implemented when switching inductive loads.
Spark suppression with inductive AC loads
Must be performed externally according to
driven load specification
Switching frequencies
With resistive loads
Max. 1 Hz
With inductive loads
On request
With lamp loads
On request
Short-circuit-proof / Overload-proof
No, should be provided by an external fuse
or circuit breaker
Rated protection fuse (for each channel)
On request
Overload message
No
Output current limitation
No
Resistance to feedback against 24 V DC
No
Connection of 2 outputs in parallel
Not possible
Lifetime of relay contacts (cycles)
100,000 at rated load
Max. cable length *)
Shielded
On request
Unshielded
On request
*) For fast inputs and fast outputs including PTO and PWM, a shielded cable must be used and
the max. cable length is 50 m.
Technical data of the limit switch outputs
Parameter
PM5012-T-ETH PM5012-R-ETH PM5032-T-ETH
PM5052-T-ETH
PM5072-
T-2ETH
PM5032-R-
ETH
PM5052-R-
ETH
Limit switch
Useable outputs
4
-
8
2
Fast output
max. 5 kHz
DO0 ... DO3
-
DO0 … DO3
-
Fast output,
max. 100 kHz
-
-
DO4 … DO7
DC12 … DC13
Device specifications
Processor modules > AC500-eCo
2022/01/31
3ADR010278, 3, en_US
42