Table 84: Output channel 0 (1 channel)
No.
Name
Value
Internal value Internal
value, type
Default
1
Channel con-
figuration
see table
4
)
see table
4
)
Byte
see table
4
)
2
Channel mon-
itoring
see table
5
)
see table
5
)
Byte
see table
5
)
3
Substitute
value
see table
6
)
0...65535
0...
0xffff
Word
0
Table 85: Output channels 1...7 (7x)
No.
Name
Internal value, type Default
1
Channel configura-
tion
see table
4
)
Byte
see table
4
)
2
Channel monitoring
see table
5
)
Byte
see table
5
)
Table 86: Channel configuration
4
)
Internal value Operating modes of the analog outputs, individually configurable
0
Unused (default)
128
Analog output -10 V...+10 V
129
Analog output 0 mA...20 mA (not with the channels 4...7)
130
Analog output 4 mA...20 mA (not with the channels 4...7)
Table 87: Channel monitoring
5
)
Internal value Monitoring
0
Plausibility, open circuit (broken wire) and short circuit (default)
1
Open-circuit (broken wire) and short-circuit
2
Plausibility
3
No monitoring
Table 88: Substitute value
6
)
Intended behavior of output
channel when the control
system stops
Required setting of the
module parameter "Behav-
iour of outputs in case of a
communication error"
Required setting of the
channel parameter "Substi-
tute value"
Output OFF
Off
0
Last value
Last value
0
Substitute value
Off or last value
1...65535
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US