3
)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or FBP: 31 = module itself; COM1/COM2: 1...10 = expan-
sion 1...10
Channel error: I/O bus or FBP = module type (1 = AI, 3 = AO); COM1/COM2:
1...10 = expansion 1...10
4
)
In case of module errors, with channel "31 = Module itself" is output.
State LEDs
During the power ON procedure, the module initializes automatically. All LEDs (except the
channel LEDs) are ON during this time.
LED
State
Color
LED = OFF
LED = ON
LED flashes
Inputs/
outputs
00...07
Analog input/
output
Yellow Input/output
is OFF
Input/output is
ON (bright-
ness depends
on the value
of the analog
signal)
--
UP
Process
voltage
24 V DC via
terminal
Green Process
voltage is
missing
Process
voltage OK
--
CH-ERR3
Channel
error, error
messages
combined
into group 3
Red
No error or
process
voltage is
missing
Severe error
within the cor-
responding
group
Error on one
channel of the
group
Measuring ranges
Input ranges of voltage, current and digital input
The represented resolution corresponds to 16 bits.
Range
0...10 V
-10...+10
V
0...20 mA 4...20 mA Digital
input
Digital value
Decimal
Hex.
Overflow
>11.7589
>11.7589
>23.5178
>22.8142
32767
7FFF
Measured
value too
high
11.7589
:
10.0004
11.7589
:
10.0004
23.5178
:
20.0007
22.8142
:
20.0006
32511
:
27649
7EFF
:
6C01
Normal
range
Normal
range or
measured
value too
low
10.0000
:
0.0004
10.0000
:
0.0004
20.0000
:
0.0007
20.0000
:
4.0006
ON
27648
:
1
6C00
:
0001
0.0000
0.0000
0
4
OFF
0
0000
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
426