1
)
In AC500, the following interface identifier applies:
14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2.
The FBP diagnosis block does not contain this identifier.
2
)
With "Device" the following allocation applies:
31 = module itself, 1..10 = expansion module 1...10, ADR = hardware address
(e.g. of the DC551)
3
)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or FBP: 31 = module itself; COM1/COM2: 1..10 =
expansion 1...10
Channel error: I/O bus or FBP = module type (1 = AI); COM1/COM2: 1..10 =
expansion 1...10
4
)
In case of module errors, with channel "31 = Module itself" is output.
State LEDs
During the power ON procedure, the module initializes automatically. All LEDs (except the
channel LEDs) are ON during this time.
LED
State
Color
LED = OFF
LED = ON
LED flashes
Inputs
I0...I7 and
I8...I15
Analog input Yellow Input is OFF Input is ON
(brightness
depends on
the value of
the analog
signal)
--
UP
Process
voltage
24 V DC via
terminal
Green Process
voltage is
missing
Process
voltage OK
--
CH-ERR2
Channel
error, error
messages in
groups
(analog
inputs or out-
puts com-
bined into the
groups 2 and
4)
Red
No error or
process
voltage is
missing
Severe error
within the cor-
responding
group
Error on one
channel of the
group
CH-ERR4
Red
CH-ERR *) Module error Red
--
Internal error
--
*) Both LEDs (CH-ERR2 and CH-ERR4) light up together
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
448