Range
Pt100 / Pt
1000
-50...70 °C
Pt100 /
Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal
Hex.
Normal
range
:
:
70.0 °C
:
0.1 °C
400.0 °C
:
:
:
0.1 °C
:
150.0 °C
:
:
0.1 °C
4000
1500
700
:
1
0FA0
05DC
02BC
:
0001
0.0 °C
0.0 °C
0.0 °C
0
0000
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-1
:
-500
FFFF
:
FE0C
Measured
value too low
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-501
:
-600
FE0B
:
FDA8
Underflow
< -60.0 °C
< -60.0 °C
< -60.0 °C
-32768
8000
Technical data
The system data of AC500 and S500
Chapter 2.6.1 “System data AC500” on page 971
are
applicable to the standard version.
The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Value
Process voltage
Connections
Terminals 1.8, 2.8, 3.8 and 4.8 for +24
V (UP) as well as 1.9, 2.9, 3.9 and 4.9
for 0 V (ZP)
Rated value
24 V DC
Max. ripple
5 %
Protection against reversed voltage
Yes
Rated protection fuse on UP
10 A fast
Galvanic isolation
Yes, per module
Current consumption
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication
interface module
Ca. 2 mA
From UP at normal operation / with outputs
0.15 A + output loads
Inrush current from UP (at power up)
0.050 A
2
s
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
450