Connection of active-type analog sensors (Voltage) with galvanically isolated power supply
UP
ZP
1.0
I0-
1.1
I0B
1.8
UP
1.9
ZP
PTC
2.0
I0+
2.1
I0A
2.8
UP
2.9
ZP
-50 ... +50 mV
-500 ... +500 mV
-1 ... +1 V
-5 ... +5 V
-10 ... +10 V
-50 ... +50 mV
0 ... +5 V
0 ... +10 V
+
-
U
IN
Fig. 34: Connection example
The measuring ranges can be configured
Chapter 1.6.2.2.3.6 “Parameterization”
Voltage
-50 mV...+50 mV
1 channel used
Voltage
-500 mV...+500 mV
1 channel used
Voltage
-1 V...+1 V
1 channel used
Voltage
-5 V...+5 V
1 channel used
Voltage
-10 V...+10 V
1 channel used
Voltage
0 V...+5 V
1 channel used
Voltage
0 V...+10 V
1 channel used
Fig. 35: Connection example
The measuring range can be configured
Chapter 1.6.2.2.3.6 “Parameterization” on page 472
Voltage
Common mode voltage
1 channel used
Standard ranges
Common mode
range (+/-20 V)
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
458