Range
Typ J
-210 ...
+1200 °C
Typ K
-270 ...
+1372 °C
Typ N
-270 ...
+1300 °C
Typ S
-50 ...
+1768 °C
Typ T
-270 ...
+400 °C
Digital value
Decimal
Hex.
0.1 °C
0.1 °C
0.1 °C
0.1 °C
0.1 °C
1
1
0.0 °C
0.0 °C
0.0 °C
0.0 °C
0
0000
-0.1 °C
-0.1 °C
-0.1 °C
-0.1 °C
-0.1 °C
-1
FFFF
:
:
:
:
:
:
:
:
:
:
-50.0 °C
:
-500
FE0C
-210.0 °C :
:
:
:
-2100
F7CC
-270.0 °C -270.0 °C
-270.0 °C -2700
F574
Under-
flow
< -210.0
°C
< -270.0
°C
< -270.0
°C
< -50.0
°C
< -270.0
°C
-32768
8000
Temperature-internal reference point ranges
Range
Value
Digital value
Decimal
Hex.
Overflow
> +85 °C
32767
7FFF
Normal range
+85 °C
850
0352
0 °C
0
0000
-40 °C
-400
FE70
Underflow
< -40 °C
-32768
8000
Technical data
The system data of AC500 and S500
Chapter 2.6.1 “System data AC500” on page 971
are
applicable to the standard version.
The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter
Value
Process voltage
Connections
Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V
(UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V
(ZP)
Rated value
24 V DC
Max. ripple
5 %
Protection against reversed voltage
Yes
Rated protection fuse on UP
10 A fast
Galvanic isolation
Yes, per module
Current consumption
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
482