● 4 mA...20 mA
● Pt100, -50 °C...+400 °C (2-wire)
● Pt100, -50 °C...+400 °C (3-wire), requires 2 channels
● Pt100, -50 °C...+70 °C (2-wire)
● Pt100, -50 °C...+70 °C (3-wire), requires 2 channels
● Pt1000, -50 °C...+400 °C (2-wire)
● Pt1000, -50 °C...+400 °C (3-wire), requires 2 channels
● Ni1000, -50 °C...+150 °C (2-wire)
● Ni1000, -50 °C...+150 °C (3-wire), requires 2 channels
● 0 V...10 V with differential inputs, requires 2 channels
● -10 V...+10 V with differential inputs, requires 2 channels
● Digital signals (digital input)
4 analog outputs (O0...O3), individually configurable for
● Unused (default setting)
● -10 V...+10 V
● 0 mA...20 mA
● 4 mA...20 mA
4 analog outputs (O4...O7), individually configurable for
● Unused (default setting)
● -10 V...+10 V
Parameter
Value
Resolution of the analog channels
Voltage -10 V...+10 V
12 bits plus sign
Voltage 0 V...10 V
12 bits
Current 0 mA...20 mA, 4 mA...20 mA 12 bits
Temperature
0.1 °C
LED displays
19 LEDs for signals and error messages
Internal power supply
Via the I/O bus interface (I/O bus)
External power supply
Via the terminals ZP and UP (process voltage
24 V DC)
Required terminal unit
TU516, TU541 and TU542 for I/O modules”
Connections
For a detailed description of the mounting, disassembly and connection of the
module, please refer to the System Assembly, Construction and Connection
Chapter 2.6 “AC500 (Standard)” on page 971.
The modules are plugged on an I/O terminal unit
Chapter 1.5.2 “TU515, TU516, TU541 and
TU542 for I/O modules” on page 126
. Properly position the modules and press until they lock
in place. The terminal units are mounted on a DIN rail or with 2 screws plus the additional
accessory for wall mounting (TA526
Chapter 1.8.2.6 “TA526 - Wall mounting accessory”
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
525