Internal value Operating modes of the analog inputs, individually configurable
4
Analog input 4 mA...20 mA
5
Analog input -10 V...+10 V
8
Analog input Pt100, -50 °C...+400 °C (2-wire)
9
Analog input Pt100, -50 °C...+400 °C (3-wire), requires 2 channels *)
10
Analog input 0...10 V via differential inputs, requires 2 channels *)
11
Analog input -10 V...+10 V via differential inputs, requires 2 channels *)
14
Analog input Pt100, -50 °C...+70 °C (2-wire)
15
Analog input Pt100, -50 °C...+70 °C (3-wire), requires 2 channels *)
16
Analog input Pt1000, -50 °C...+400 °C (2-wire)
17
Analog input Pt1000, -50 °C...+400 °C (3-wire), requires 2 channels *)
18
Analog input Ni1000, -50 °C...+150 °C (2-wire)
19
Analog input Ni1000, -50 °C...+150 °C (3-wire), requires 2 channels *)
*) In the operating modes with 3-wire configuration or with differential inputs,
two adjacent analog inputs belong together (e.g. the channels 0 and 1). In
these cases, both channels are configured in the desired operating mode. The
lower address must be the even address (channel 0). The next higher address
must be the odd address (channel 1). The converted analog value is available
at the higher address (channel 1).
Table 112: Channel monitoring
3
)
Internal value
Monitoring
0
Plausibility, open-circuit (broken wire) and short circuit
3
No monitoring
Table 113: Output channel 0 (1 channel)
No.
Name
Value
Internal value Internal
value, type
Default
1
Channel con-
figuration
see table
4
)
see table
4
)
Byte
see table
4
)
2
Channel mon-
itoring
see table
5
)
see table
5
)
Byte
see table
5
)
3
Substitute
value
see table
6
)
0...65535
0...
0xffff
Word
0
Table 114: Output channels 1...3 (3x)
No.
Name
Internal value, type
1
Channel configuration
see table
4
)
Byte
2
Channel monitoring
see table
6
)
Byte
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
539