E1...E4
d1
d2
d3
d4
Identifier
000...063
AC500
display
<− Display in
Class
Comp
Dev
Mod
Ch
Err
PS501
PLC
browser
Byte 6
Bit 6...7
-
Byte 3
Byte 4
Byte 5
Byte 6
Bit 0...5
FBP
diag-
nosis
block
Class
Interface Device
Module
Channel
Error
Identifier
Error message
Remedy
1
)
2
)
3
)
4
)
4
14
1...10
1
0...3
0...7
48
Analog value over-
flow or broken wire
at an analog input
Check
input
value or
terminal
11 / 12
ADR
1...10
4
14
1...10
1
0...3
0...7
7
Analog value under-
flow at an analog
input
Check
input
value
11 / 12
ADR
1...10
4
14
1...10
1
0...3
0...7
47
Short circuit at an
analog input
Check
terminal
11 / 12
ADR
1...10
4
14
1...10
3
4...7
8...15
4
Analog value over-
flow at an analog
output
Check
output
value
11 / 12
ADR
1...10
4
14
1...10
3
4...7
8...15
7
Analog value under-
flow at an analog
output
Check
output
value
11 / 12
ADR
1...10
Remarks:
1
)
In AC500, the following interface identifier applies:
14 = I/O bus, 11 = COM1 (e.g. CS31 bus), 12 = COM2.
The FBP diagnosis block does not contain this identifier.
2
)
With "Device" the following allocation applies:
31 = module itself, 1...10 = expansion module 1...10, ADR = hardware address
(e.g. of the DC551)
3
)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or FBP: 31 = module itself; COM1/COM2: 1...10 = expan-
sion 1...10
Channel error: I/O bus or FBP = module type (1 = AI, 3 = AO); COM1/COM2:
1...10 = expansion 1...10
4
)
In case of module errors, with channel "31 = Module itself" is output.
State LEDs
During the power ON procedure, the module initializes automatically. All LEDs (except the
channel LEDs) are ON during this time.
Device specifications
I/O modules > Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
542