Parameter
Value
Settling time for full range change (resistive
load, output signal within specified tolerance)
Typ. 5 ms
Conversion error of the analog values caused
by non-linearity, adjustment error at factory
and resolution within the normal range
Typ.
±
0.5 % of full scale
at 25 °C
Max.
±
1 % of full scale (all ranges)
at 0 °C...60 °C or EMC disturbance
Relationship between output signal and hex
code
See table,
ranges voltage and current” on page 544
Unused outputs
Can be left open-circuited
Ordering data
Part no.
Description
Product life cycle phase *)
1SAP 250 000 R0001 AX522, analog input/output module,
8 AI, 8 AO, U/I/Pt100, 12 bits + sign,
2-wires
Active
1SAP 450 000 R0001 AX522-XC, analog input/output
module, 8 AI, 8 AO, U/I/Pt100,
12 bits + sign, 2-wires, XC version
Active
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
1.6.3 Digital/Analog I/O modules
1.6.3.1
S500
1.6.3.1.1 DA501 - Digital/Analog input/output module
● 16 digital inputs 24 V DC
● 8 configurable digital inputs/outputs 24 V DC, 0.5 A max.
● 4 analog inputs, voltage, current and RTD.
Resolution 12 bits plus sign
● 2 analog outputs, voltage and current
Resolution 12 bits plus sign
● Fast counter
● Module-wise galvanically isolated
● XC version for use in extreme ambient conditions available
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
548