Parameter
Value
Galvanic isolation
Against internal supply and other modules
Configurability
-10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA
(each output can be configured individually)
Output resistance (load) as current output
0
W
...500
W
Output loadability as voltage output
±
10 mA max.
Indication of the output signals
1 LED per channel (brightness depends on the
value of the analog signal)
Resolution
12 bits (+ sign)
Settling time for full range change (resistive
load, output signal within specified tolerance)
Typ. 5 ms
Conversion error of the analog values caused
by non-linearity, adjustment error at factory
and resolution within the normal range
Typ. 0.5 %, max. 1 %
Relationship between input signal and hex
code
Chapter 1.6.3.1.1.9.3 “Output ranges
voltage and current” on page 575
Unused outputs
Are configured as "unused" (default value) and
can be left open-circuited
Internal data exchange
Without the fast counter
With the fast counter (only
with AC500)
Digital inputs (bytes)
3
5
Digital outputs (bytes)
1
3
Analog inputs (words)
4
4
Analog outputs (words)
2
2
Counter input data (words)
0
4
Counter output data (words)
0
8
Ordering data
Part no.
Description
Product life cycle phase *)
1SAP 250 700 R0001 DA501, digital/analog input/output
module, 16 DI, 8 DC, 4 AI, 2 AO
Active
1SAP 450 700 R0001 DA501-XC, digital/analog input/output
module, 16 DI, 8 DC, 4 AI, 2 AO,
XC version
Active
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
582