Parameter
Value
Process supply voltage
Connections
Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24
V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0
V)
Protection against reverse voltage
yes
Rated protection fuse at UP
10 A fast
Rated value
24 V DC
Max. ripple
5 %
Current consumption
From UP
0.07 A + max. 0.5 A per output
From 24 V DC power supply at the termi-
nals UP/L+ and ZP/M of the CPU/communi-
cation interface module
ca. 2 mA
Inrush current from UP (at power-up)
0.04 A
2
s
Galvanic isolation
Yes, per module
Max. power dissipation within the module
6 W (outputs unloaded)
Weight (without terminal unit)
ca. 125 g
Mounting position
Horizontal mounting or vertical with
derating (output load reduced to 50% at 40
°C)
Cooling
The natural convection cooling must not be
hindered by cable ducts or other parts in
the switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Technical data of the digital outputs
Parameter
Value
Number of channels per module
16 outputs (with transistors)
Distribution of the channels into groups
1 group of 16 channels
Connection of the channels
DO0 to DO7
Terminals 1.0 to 1.7
DO8 to DO15
Terminals 2.0 to 2.7
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
609