1.
In the device tree, double-click the desired option board.
2.
Select the
“TA51xx Parameters”
tab to edit the parameterization of the desired option
board.
1.
In the device tree, double-click the desired option board.
2.
Select the
“Diagnosis”
tab to view the diagnosis messages of the desired option board.
Table 27: Diagnosis messages
Device
Severity
Error
code
Description
Error Message
Remedy
TA5105-4DOT
11
1
Wrong or no board
plugged
Replace with correct func-
tional board
TA5105-4DOT
11
2
Board defective
Replace with correct func-
tional board
TA5105-4DOT
11
3
Failed to set direction
Replace with correct func-
tional board
TA5105-4DOT
11
4
Parameter wrong
Verify setting of parameter
“Run on config fault”
Diagnosis
Device specifications
Processor modules > AC500-eCo
2022/01/31
3ADR010278, 3, en_US
61