Parameter
Value
Indication of the output signals
1 yellow LED per channel, the LED is ON if the
output signal is high (signal 1)
Monitoring point of output indicator
LED is controlled by process CPU
Reference potential for all outputs
Terminals 1.9, 2.9, 3.9 and 4.9 (negative pole of
the process supply voltage, signal name ZP)
Common power supply voltage
For all outputs: terminals 1.8, 2.8, 3.8 and 4.8
(positive pole of the process supply voltage,
signal name UP)
Output voltage for signal 1
UP (-0.8 V)
Output delay (0->1 or 1->0)
On request
Output current
Rated value, per channel
500 mA at UP = 24 V
Maximum value (channels O0 to O15)
4 A
Leakage current with signal 0
< 0.5 mA
Rated protection fuse on UP
10 A fast
Demagnetization when inductive loads are
switched off
With varistors integrated in the module (see
figure below)
Switching frequency
With resistive load
On request
With inductive loads
Max. 0.5 Hz
With lamp loads
Max. 11 Hz with max. 5 W
Short-circuit-proof / overload-proof
Yes
Overload message (I > 0.7 A)
Yes, after ca. 100 ms
Output current limitation
Yes, automatic reactivation after short cir-
cuit/overload
Resistance to feedback against 24 V signals Yes
Max. cable length
Shielded
1000 m
Unshielded
600 m
Technical data of the configurable digital inputs/outputs
Each of the configurable digital I/O channels can be defined as input or output by the user
program. This is done by interrogating or allocating the corresponding channel.
Parameter
Value
Number of channels per module
8 inputs/outputs (with transistors)
Distribution of the channels into groups
1 group for 8 channels
If the channels are used as inputs
Channels DC16...DC23
Terminals 4.0...4.7
If the channels are used as outputs
Channels DC16...DC23
Terminals 4.0...4.7
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31
3ADR010278, 3, en_US