Parameter
Value
Relationship between input signal and hex
code
Chapter 1.6.3.1.2.9.1 “Input ranges voltage,
current and digital input” on page 606
Chapter 1.6.3.1.2.9.2 “Input ranges resist-
ance temperature detector” on page 607
Unused inputs
Are configured as "unused" (default value)
Overvoltage protection
Yes
Technical data of the analog inputs, if used as digital inputs
Parameter
Value
Number of channels per module
Max. 4
Distribution of channels into groups
1 group of 4 channels
Connections of the channels AI0+ to AI3+
Terminals 3.0 to 3.3
Reference potential for the inputs
Terminals 1.9, 2.9, 3.9 and 4.9 (ZP)
Indication of the input signals
1 LED per channel
Input signal voltage
24 V DC
Signal 0
-30 V...+5 V
Undefined signal
+5 V...+13 V
Signal 1
+13 V...+30 V
Input current per channel
Input v24 V
Typ. 7 mA
Input v5 V
Typ. 1.4 mA
Input v15 V
Typ. 3.7 mA
Input v30 V
< 9 mA
Input resistance
ca. 3.5 k
W
Technical data of the analog outputs
Parameter
Value
Number of channels per module
2
Distribution of channels into groups
1 group for 2 channels
Connection of the channels AO0+...AO1+
Terminals 3.5 and 3.6
Reference potential for AO0+ to AO1+
Terminal 3.7 (AO-) for voltage output
Terminals 1.9, 2.9, 3.9 and 4.9 for current
output
Output type
Unipolar
Current
Bipolar
Voltage
Galvanic isolation
Against internal supply and other modules
Configurability
-10 V...+10 V, 0 mA...20 mA, 4 mA...20 mA
(each output can be configured individually)
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31
3ADR010278, 3, en_US