-10 ... +10 V
0 ... +10 V
Fig. 107: Connection of active-type sensors (voltage) with no galvanically isolated power supply
to the analog inputs
NOTICE!
Risk of faulty measurements!
The negative pole/ground potential at the sensors must not have too large a
potential difference with respect to ZP (max.
±
1 V within the full signal range).
Make sure that the potential difference never exceeds
±
1 V.
Voltage
0...10 V
1 channel used
Voltage
-10 V...+10 V
1 channel used
For the measuring ranges that can be configured, plese refer to the sections Measuring Ranges
Chapter 1.7.2.2.10 “Measuring ranges” on page 650
1.7.2.2.7 “Parameterization” on page 640
To avoid error messages, configure unused analog input channels as "unused".
Connection of passive-type analog sensors (Current) to the analog inputs
The following figure shows the connection of passive-type analog sensors (current) to the
analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.