Parameter
Value
Ambient temperature
System data AC500
System data AC500 XC
“System data AC500-XC” on page 1023
Current consumption
UP: 0.2 A UP3: 0.06 A + 0.5 A max. per output
Weight (without terminal unit)
Ca. 125 g
Process supply voltages UP/UP3
Rated value
24 V DC (for inputs and outputs)
Max. load for the terminals
10 A
Protection against reversed voltage
Yes
Rated protection fuse on UP/UP3
10 A fast
Galvanic isolation
CANopen interface against the rest of the
module
Inrush current from UP (at power up)
On request
Current consumption via UP (normal
operation)
0.2 A
Current consumption via UP3
0.06 A + 0.5 A max. per output
Connections
Terminals 2.8 and 3.8 for +24 V (UP)
Terminal 4.8 for +24 V (UP3)
Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)
Max. power dissipation within the module
6 W
Reference potential for all digital inputs and
outputs
Negative pole of the supply voltage, signal
name ZP
Setting of the CANopen Node ID identifier
With 2 rotary switches at the front side of the
module
Mounting position
Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
Cooling
The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Effect of incorrect input terminal connection
Wrong or no signal detected, no damage up to
35 V
Required terminal unit
TU509, TU510, TU517 or TU518
Chapter 1.5.3 “TU517 and TU518 for com-
munication interface modules” on page 132
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Device specifications
Communication interface modules (S500) > CANopen
2022/01/31
3ADR010278, 3, en_US
659