Name
Value
Internal value
Internal value,
type
Default
Substitute value
at output
0 ... 65535
0000h ... FFFFh
WORD
0
0x0000
Preventive
voltage feedback
monitoring for
DC0..DC7
2
)
Off
On
0
1
BYTE
Off
0x00
Detect voltage
overflow at out-
puts
3
)
Off
On
0
1
BYTE
Off
0x00
Remarks:
1
)
The parameter Behavior DO at comm. error is applied to DC and DO
channels and only analyzed if the failsafe mode is ON.
2
)
The state "externally voltage detected" appears if the output of a channel
DC0..DC7 is to be switched on while an external voltage is connected.
In this case, start-up is disabled while the externally voltage is con-
nected. The monitoring of this state and the resulting diagnosis message
can be disabled by setting the parameters to "OFF".
3
)
The error state "voltage overflow at outputs" appears if external voltage
at digital outputs DC0..DC7 and DO0..DO7 has exceeded the process
supply voltage UP3 (see 'Connections'
). The according diagnosis message "Voltage over-
flow on outputs " can be disabled by setting the parameters to "OFF".
This parameter should only be disabled in exceptional cases as voltage
overflow may produce reverse voltage.
1.7.2.3.8 Diagnosis
Byte Number
Description
Possible Values
1
Diagnosis byte, slot number 31 = CI582-CN (e. g. error at integrated 8 DI /
8 DO)
1 = 1st connected S500 I/O module
...
10 = 10th connected S500 I/O module
2
Diagnosis byte, module
number
According to the I/O bus specification passed
on by modules to the fieldbus master
3
Diagnosis byte, channel
According to the I/O bus specification passed
on by modules to the fieldbus master
Device specifications
Communication interface modules (S500) > CANopen
2022/01/31
3ADR010278, 3, en_US
670