0...10 V
AGND
1.0
1.1
1.8
1.9
AI0+
AI1+
UP
ZP
UP
ZP
PTC
1.5
AI–
UP (remote)
ZP (remote)
1
2
3
Fig. 127: Connection of active-type sensors (voltage) with no galvanically isolated power supply
1
1 analog sensor requires 1 channel
2
Power supply not galvanically isolated
3
The connection between the negative pole of the sensor and ZP has to be performed
4
Long cable
NOTICE!
Risk of faulty measurements!
The negative pole/ground potential at the sensors must not have too large a
potential difference with respect to ZP (max.
±
1 V within the full signal range).
Make sure that the potential difference never exceeds
±
1 V.
Voltage
0...10 V
1 channel used
Voltage
-10 V...+10 V *)
1 channel used
*) if the sensor can provide this signal range
The measuring ranges are described in the section Measuring Ranges
“Parameterization” on page 694
Chapter 1.7.3.1.10 “Measuring ranges” on page 703
.
In order to avoid error messages or long processing times, it is useful to configure unused
analog input channels as "unused".
Connection of passive-type analog sensors (Current)
The following figure shows the connection of passive-type analog sensors (current).