Group parameters for the analog part
Name
Value
Internal value
Internal value,
type
Default
Analog data
format
Standard
0
BYTE
0
Behaviour AO at
comm. error *)
Off
Last value
Last value 5 s
Last value 10 s
Substitute value
Substitute value
5 s
Substitute value
10 s
0
1
6
11
2
7
12
BYTE
0
*) The parameter Behaviour AO at comm. error is only analyzed if the Failsafe-mode is ON.
Channel parameters for the analog inputs (4x)
Name
Value
Internal value
Internal value,
type
Default
Input 0, channel
configuration
see
1
)
see
1
)
BYTE
0
Input 0, check
channel
see
2
)
see
2
)
BYTE
0
:
:
:
:
:
:
:
:
:
:
Input 3, channel
configuration
see
1
)
see
1
)
BYTE
0
Input 3, channel
configuration
see
2
)
see
2
)
BYTE
0
Internal value
Operating modes of the analog inputs, individually configurable
0 (default)
Not used
1
0...10 V
2
Digital input
3
0...20 mA
4
4...20 mA
5
-10 V...+10 V
8
2-wire Pt100 -50...+400 °C
9
3-wire Pt100 -50...+400 °C *)
10
0 V...10 V (voltage diff.) *)
11
-10 V...+10 V (voltage diff.) *)
14
2-wire Pt100 -50...+70 °C
15
3-wire Pt100 -50...+70 °C *)
Channel config-
uration
1
)
Device specifications
Communication interface modules (S500) > EtherCAT
2022/01/31
3ADR010278, 3, en_US
697