E1..E4
d1
d2
d3
d4
Identifier
000..063
AC500-
Display
<− Display in
Class
Comp
Dev
Mod
Ch
Err
PS501
PLC
Browser
Byte 6
Bit 6..7
-
Byte 3
Byte 4
Byte 5
Byte 6
Bit 0..5
ETHCAT
Diagnosis
block
Class
Interface
Device
Module
Channel
Error
identifier
Error message
Remedy
1
)
2
)
3
)
4
-
31
31
31
45
Process voltage UP3
too low
Check
process
voltage
4
-
31
31
31
34
No response during ini-
tialization of the I/O
module
Replace
I/O module
4
-
31
31
31
46
Voltage feedback on
activated digital outputs
4
)
Check ter-
minals
Channel error digital
4
-
31
2
0..15
46
Voltage feedback on
deactivated digital
output
5
)
Check ter-
minals
4
-
31
4
0..7
47
Short circuit at digital
output
Check ter-
minals
4
-
31
2
8..15
47
Short circuit at digital
output
Check ter-
minals
Remarks:
1
)
In AC500 the following interface identifier applies:
"-" = Diagnosis via bus-specific function blocks; 0 ... 4 or 10 = Position of the
Communication Module; 14 = I/O bus; 31 = Module itself
The identifier is not contained in the CI512-ETHCAT diagnosis block.
2
)
With "Device" the following allocation applies:
31 = Module itself or ADR = Hardware address (e. g. of the DC551)
3
)
With "Module" the following allocation applies dependent of the master:
31 = Module itself (Module error) or Module type (1=AI, 2=DO, 3=AO; channel
error)
4
)
Diagnosis message appears for the whole output group and not per channel.
The message occurs if the output channel is already active.
5
Diagnosis message appears per channel. The message occurs if the output
channel is not active.
1.7.3.2.10
State LEDs
The LEDs are located at the front of module. There are 2 different groups:
Device specifications
Communication interface modules (S500) > EtherCAT
2022/01/31
3ADR010278, 3, en_US
721