Output ranges voltage and current
Range
-10...+10 V
0...20 mA
4...20 mA
Digital value
Decimal
Hex.
Overflow
0 V
0 mA
0 mA
> 32511
> 7EFF
Measured
value too high
11.7589 V
:
10.0004 V
23.5178 mA
:
20.0007 mA
22.8142 mA
:
20.0006 mA
32511
:
27649
7EFF
:
6C01
Normal range 10.0000 V
:
0.0004 V
20.0000 mA
:
0,0007 mA
20.0000 mA
:
4.0006 mA
27648
:
1
6C00
:
0001
0.0000 V
0.0000 mA
4.0000 mA
0
0000
-0.0004 V
:
-10.0000 V
0 mA
:
0 mA
3.9994 mA
0 mA
0 mA
-1
-6912
-27648
FFFF
E500
9400
Measured
value too low
-10.0004 V
:
-11.7589 V
0 mA
:
0 mA
0 mA
:
0 mA
-27649
:
-32512
93FF
:
8100
Underflow
0 V
0 mA
0 mA
< -32512
< 8100
The represented resolution corresponds to 16 bits.
1.7.4.1.10
Technical data
The system data of AC500 and S500
Chapter 2.6.1 “System data AC500” on page 971
are
applicable to the standard version.
The system data of AC500-XC
Chapter 2.7.1 “System data AC500-XC” on page 1023
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Technical data of the module
Parameter
Value
Process supply voltages UP/UP3
Rated value
24 V DC (for inputs and outputs)
Max. load for the terminals
10 A
Protection against reversed voltage
Yes
Rated protection fuse on UP/UP3
10 A fast
Galvanic isolation
Ethernet interface against the rest of the
module
Inrush current from UP (at power up)
On request
Current consumption via UP (normal
operation)
0.2 A
Current consumption via UP3
0.06 A + 0.5 A max. per output
Device specifications
Communication interface modules (S500) > Modbus
2022/01/31
3ADR010278, 3, en_US
763