Do not connect any voltages externally to digital outputs!
This ist not intended usage.
Reason: Externally voltages at one or more terminals DC0...DC7 or
DO8...DO15 may cause that other digital outputs are supplied through that
voltage instead of voltage UP3 (reverse voltage).
This is also possible, if DC channels are used as inputs. For this, the source for
the input signals should be the impressed UP3 of the device.
This limitation does not apply for the input channels DI0..DI7.
CAUTION!
Risk of malfunction by unintended usage!
If the function cut-off of the digital outputs is to be used by deactivation of the
supply voltage UP3, be sure that no external voltage is conncted at the outputs
DO8...DO15 and DC0...DC7.
The assignment of the other terminals:
Terminal
Signal
Description
1.0
DC0
Signal of the configurable digital input/output
DC0
1.1
DC1
Signal of the configurable digital input/output
DC1
1.2
DC2
Signal of the configurable digital input/output
DC2
1.3
DC3
Signal of the configurable digital input/output
DC3
1.4
DC4
Signal of the configurable digital input/output
DC4
1.5
DC5
Signal of the configurable digital input/output
DC5
1.6
DC6
Signal of the configurable digital input/output
DC6
1.7
DC7
Signal of the configurable digital input/output
DC7
1.8
UP
Process voltage UP (24 V DC)
1.9
ZP
Process voltage ZP (0 V DC)