Interface
PIN
Signal
Description
8
NC
Not connected
Shield
Cable shield
Functional earth
In corrosive environment, please protect unused connectors using the TA535
accessory.
Not supplied with this device.
For further information regarding wiring and cable types see chapter Ethernet
Chapter 2.6.4.7 “Ethernet connection details” on page 997.
1.7.5.2.4 Internal data exchange
Parameter
Value
Digital inputs (bytes)
3
Digital outputs (bytes)
3
Analog inputs (words)
4
Analog outputs (words)
2
Counter input data (words)
4
Counter output data (words)
8
1.7.5.2.5 Addressing
The module reads the position of the rotary switches only during power-up, i. e.
changes of the switch position during operation will have no effect until the next
module initialization.
1.7.5.2.6 I/O configuration
The CI501-PNIO stores some PROFINET configuration parameters (I/O device identifier, I/O
device type and IP address configuration). No more configuration data is stored.
The analog/digital I/O channels are configured via software.
Details about configuration are described in Parameterization
Chapter 1.7.5.2.7 “Parameteri-
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
814