Channel parameters for the analog inputs (4x)
Name
Value
Internal value
Internal value,
type
Default
Input 0, Channel
configuration
Table Operating
modes of the
analog inputs
Table Operating
modes of the
BYTE
0
Input 0, Check
channel
Table Channel
Table Channel
montoring
BYTE
0
:
:
:
:
:
:
:
:
:
:
Input 3, Channel
configuration
Table Operating
modes of the
analog inputs
Table Operating
modes of the
BYTE
0
Input 3, Check
channel
Table Channel
Table Channel
montoring
BYTE
0
Table 167: Channel configuration
Internal value
Operating modes of the analog inputs, individually configurable
0 (default)
Not used
1
0 V...10 V
2
Digital input
3
0 mA...20 mA
4
4 mA...20 mA
5
-10 V...+10 V
8
2-wire Pt100 -50 °C...+400 °C
9
3-wire Pt100 -50 °C...+400 °C *)
10
0 V...10 V (voltage diff.) *)
11
-10 V...+10 V (voltage diff.) *)
14
2-wire Pt100 -50 °C...+70 °C
15
3-wire Pt100 -50 °C...+70 °C *)
16
2-wire Pt1000 -50 °C...+400 °C
17
3-wire Pt1000 -50 °C...+400 °C *)
18
2-wire Ni1000 -50 °C...+150 °C
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
818