1.7.5.2.9 Measuring ranges
Input ranges voltage, current and digital input
Range
0...10 V
-10...+10
V
0...20 mA 4...20 mA Digital
input
Digital value
Decimal
Hex.
Overflow
>11.7589 >11.7589 >23.5178 >22.8142
32767
7FFF
Measured
value too
high
11.7589
:
10.0004
11.7589
:
10.0004
23.5178
:
20.0007
22.8142
:
20.0006
32511
:
27649
7EFF
:
6C01
Normal
range
Normal
range or
measured
value too
low
10.0000
:
0.0004
10.0000
:
0.0004
20.0000
:
0.0007
20.0000
:
4.0006
:
:
On
27648
:
1
6C00
:
0001
0.0000
0.0000
0
4
Off
0
0000
-0.0004
-1.7593
-0.0004
:
:
:
-10.0000
3.9994
:
0
-1
-4864
-6912
:
-27648
FFFF
ED00
E500
:
9400
Measured
value too
low
-10.0004
:
-11.7589
-27649
:
-32512
93FF
:
8100
Under-
flow
<0.0000
<-11.7589 <0.0000
<0.0000
-32768
8000
The represented resolution corresponds to 16 bits.
Input ranges resistance temperature detector
Range
Pt100 / Pt1000
-50...+70 °C
Pt100 /
Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal
Hex.
Overflow
> 80.0 °C
> 450.0 °C
> 160.0 °C
32767
7FFF
Measured
value too
high
80.0 °C
450.0 °C
:
400.1 °C
4500
:
4001
1194
:
0FA1
160.0 °C
:
150.1 °C
1600
:
1501
0640
:
05DD
Normal
range
400.0 °C
:
:
:
0.1 °C
150.0 °C
:
:
0.1 °C
800
:
701
0320
:
02BD
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
828