Technical data of the fast counter
Parameter
Value
Used inputs
Terminal 2.0 (DI0), 2.1 (DI1)
Used outputs
Terminal 3.0 (DO0)
Counting frequency
Depending on operation mode:
Mode 1 - 6: max. 200 kHz
Mode 7: max. 50 kHz
Mode 9: max. 35 kHz
Mode 10: max. 20 kHz
1.7.5.2.11
Ordering data
Part no.
Description
Product life cycle phase *)
1SAP 220 600 R0001 CI501-PNIO (V3), PROFINET commu-
nication interface module, 8 DI, 8 DO,
4 AI and 2 AO
Active
1SAP 420 600 R0001 CI501-PNIO-XC (V3), PROFINET
communication interface module, 8 DI,
8 DO, 4 AI and 2 AO, XC version
Active
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
1.7.5.3
CI502-PNIO
● 8 digital inputs 24 V DC
● 8 digital outputs 24 V DC, 0.5 A max.
● 8 configurable digital inputs/outputs 24 V DC, 0.5 A max.
● Module-wise galvanically isolated
● Fast counter
● XC version for usage in extreme ambient conditions available
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
836