2.4.5 Power consumption of an entire station
The power consumption of a complete station consists of the sum of all individual consump-
tions.
● Consumers over terminals L+ and M on the AC500 terminal base/AC500-eCo CPU:
–
CPU itself
–
I/O modules attached on the I/O bus
–
Communication modules attached (AC500 terminal base)
● Consumers over the process supply voltage terminals ZP and UP of the AC500 terminal
units / the L+/M or UP/ZP terminals of the AC500-eCo I/O modules:
–
Digital I/O modules
–
Analog I/O modules
The two supply voltages can be provided by the same power supply unit. The CPU and the
I/O modules should, however, be fused separately. Of course also separate power supplies are
possible.
2.4.5.1
Calculation of the total current consumption
In the example, the AC500 control system consists of the following devices:
● AC500 CPU with Ethernet interface
● 4 communication modules
● 7 I/O modules (digital and analog)
● As well as the required terminal bases and terminal units
Example
System assembly, construction and connection
Overall information (valid for complete AC500 product family) > Power consumption of an entire station
2022/01/31
3ADR010278, 3, en_US
922