Parameter
Value
Vibration resistance acc. to EN 61131-2
all three axes
2 Hz...8.4 Hz, continuous 3.5 mm
8.4 Hz...150 Hz, continuous 1 g (higher values
on request)
Shock test
All three axes
15 g, 11 ms, half-sinusoidal
Mounting of the modules:
DIN rail according to DIN EN 50022
35 mm, depth 7.5 mm or 15 mm
Mounting with screws
Screws with a diameter of 4 mm
Fastening torque
1.2 Nm
2.6.1.7
Approvals and certifications
Information on approvals and certificates can be found in the corresponding chapter of the
.
2.6.2 Mechanical dimensions
2.6.2.1
Switchgear cabinet assembly
Information on EMC-conforming assembly and construction is provided within
Chapter 2.4.4 “EMC-conforming assembly and
NOTICE!
PLC damage due to wrong enclosures
Due to their construction (degree of protection IP 20 according to EN 60529)
and their connection technology, the devices are suitable only for operation in
enclosed switchgear cabinets.
To protect PLCs against:
● unauthorized access,
● dusting and pollution,
● moisture and wetness and
● mechanical damage,
switchgear cabinet IP54 for common dry factory floor environment is suitable.
Maintain spacing from:
● enclosure walls
● wireways
● adjacent equipment
Allow a minimum of 20 mm clearance on all sides. This provides ventilation and galvanic
isolation.
PLC enclosure
System assembly, construction and connection
AC500 (Standard) > Mechanical dimensions
2022/01/31
3ADR010278, 3, en_US
976