Channel parameters for the analog inputs (4x)
Name
Value
Internal value Internal
value, type
Default
EDS Slot /
Index
Input 0,
Channel con-
figuration
see
see
BYTE
0
0x0Y09
Input 0,
Check
channel
see
see
BYTE
0
0x0Y0A
:
:
:
:
:
:
:
:
:
:
Input 3,
Channel con-
figuration
see
see
BYTE
0
0x0Y0F
Input 3,
Check
channel
see
see
BYTE
0
0x0Y10
Table 120: Channel configuration
Internal value
Operating modes of the analog inputs, individually configurable
0 (default)
Not used
1
0 V...10 V
2
Digital input
3
0 mA...20 mA
4
4 mA...20 mA
5
-10 V...+10 V
8
2-wire Pt100 -50 °C...+400 °C
9
3-wire Pt100 -50 °C...+400 °C *)
10
0 V...10 V (voltage diff.) *)
11
-10 V...+10 V (voltage diff.) *)
14
2-wire Pt100 -50 °C...+70 °C
15
3-wire Pt100 -50 °C...+70 °C *)
16
2-wire Pt1000 -50 °C...+400 °C
17
3-wire Pt1000 -50 °C...+400 °C *)
18
2-wire Ni1000 -50 °C...+150 °C
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
567