Name
Value
Internal value
Internal value,
type
Default
Output 0, Substi-
tute value
Table Substitute
Table Substitute
value
WORD
0
Output 1,
Channel configu-
ration
Table Operating
modes of the
analog outputs
Table Operating
modes of the
BYTE
0
Output 1, Check
channel
Table Channel
monitoring
Table Channel
BYTE
0
Output 1, Substi-
tute value
Table Substitute
Table Substitute
value
WORD
0
Table 158: Channel configuration
Internal value
Operating modes of the analog outputs, individually configu-
rable
0 (default)
Not used
128
-10 V...+10 V
129
0...20 mA
130
4...20 mA
Table 159: Channel monitoring
Internal value
Check channel
0
Plausib(ility), cut wire, short circuit
3
None
Table 160: Substitute value
Intended behavior of output
channel when the control
system stops
Required setting of the
module parameter "Behav-
iour of outputs in case of a
communication error"
Required setting of the
channel parameter "Substi-
tute value"
Output OFF
Off
0
Last value infinite
Last value
0
Last value for 5 s and then
turn off
Last value 5 sec
0
Last value for 10 s and then
turn off
Last value 10 sec
0
Substitute value infinite
Substitute value
Depending on configuration
Device specifications
Communication interface modules (S500) > Modbus
2022/01/31
3ADR010278, 3, en_US
753