**) The needed spring terminal block is always delivered with the option board.
The terminal block listed in the table is for spare part only if needed.
1.3.1.2.7 TA5142-RS485I - Option board for COMx serial communication
1
2 LEDs for communication state display (TxD and RxD)
2
2 LEDs for termination state display
3
Allocation of signal name
4
5-pin terminal block for communication interface
Option board for COMx serial communication TA5142-RS485(I) is equipped with 1 RS-485
(2-wire half-duplex) serial interface which can be used for communication via Modbus RTU or
CAA SerialCom.
Bus terminations are built-in and configurable.
NOTICE!
Damage to the serial communication interface by using 5-pin terminal
block of the TA5101-4DI!
If the 5-pin terminal block of the TA5101-4DI option board is plugged into a
option board for COMx serial communication TA5141-RS232I, TA5142-RS485I
or TA5142-RS485, the communication interface will be damaged by the 24 V.
Please do not confuse the 5-pin terminal block of the TA5101-4DI with the 5-pin
terminal block for serial communication interface of TA5141-RS232I, TA5142-
RS485I or TA5142-RS485.
Intended pur-
pose
Connections
Serial interfaces
Device specifications
Processor modules > AC500-eCo
2022/01/31
3ADR010278, 3, en_US
78