12 Terminal unit
13 DIN rail
Sign for XC version
1.7.5.2.1 Intended purpose
The PROFINET communication interface modules CI501-PNIO and CI502-PNIO are used
as communication interface modules in PROFINET networks. The network connection is per-
formed by Ethernet cables which are inserted in the RJ45 connectors in the terminal unit. An
Ethernet switch in the communication interface module allows daisy chaining of the network.
For usage in enhanced ambient conditions (e.g. wider temperature and humidity range), a
special XC version of the device is available.
1.7.5.2.2 Functionality
The communication interface module contains 22 I/O channels with the following properties:
● 4 configurable analog inputs (2-wire / single-ended) or 2 configurable analog inputs (3-wire /
differential) (1.0...1.3)
● 2 analog outputs (1.5...1.6)
● 8 digital inputs 24 V DC in 1 group (2.0...2.7)
● 8 digital outputs 24 V DC, 0.5 A max. in 1 group (3.0...3.7)
The inputs/outputs are galvanically isolated from the PROFINET network. There is no potential
separation between the channels. The configuration of the analog inputs/outputs is performed
by software.
Parameter
Value
Interface
Ethernet
Protocol
PROFINET IO RT
Power supply
From the process supply voltage UP
Supply of the electronic circuitry of the I/O
expansion modules attached
Through the I/O bus interface (I/O bus)
Rotary switches
For setting the I/O device identifier for configu-
ration purposes (00h to FFh)
LED displays
For system displays, signal states, errors and
power supply
External supply voltage
Via terminals ZP, UP and UP3 (process supply
voltage 24 V DC)
Effect of incorrect input terminal connection
Wrong or no signal detected, no damage up to
35 V
Required terminal unit
and TU508-ETH for Ethernet communication
interface modules” on page 122
1.7.5.2.3 Connections
The Ethernet communication interface module CI501-PNIO is plugged on the I/O terminal unit
Chapter 1.5.1 “TU507-ETH and TU508-ETH for Ethernet commu-
nication interface modules” on page 122
. Properly seat the module and press until it locks in
place. The terminal unit is mounted on a DIN rail or with 2 screws plus the additional accessory
for wall mounting (TA526
Chapter 1.8.2.6 “TA526 - Wall mounting accessory” on page 902
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31
3ADR010278, 3, en_US
798