Parameter listing and descriptions
167
ACH550 User's Manual
Group 99: START-UP DATA
This group defines special start-up data required to:
• set up the drive
• enter motor information.
Code Description
Range
9901
LANGUAGE
0…16
Selects the display language.
9902
APPLIC MACRO
1…14, 0…-4
Selects an application macro. Application macros automatically edit
parameters to configure the ACH550 for a particular application.
1 =
HVAC
DEFAULT
2 =
SUPPLY
FAN
3 =
RETURN
FAN
4 =
COOLING
TOWER
FAN
5 =
CONDENSER
6 =
BOOSTER
PUMP
7 =
PUMP
ALTERNATION
8 =
INTERNAL
TIMER
9 =
INTERNAL
TIMER
WITH
CONSTANT
SPEEDS
10 =
FLOATING
POINT
11 =
DUAL
SETPOINT
PID
12 =
DUAL
SETPOINT
PID
WITH
CONSTANT
SPEEDS
13 =
E
-
BYPASS
14 =
HAND
CONTROL
0 =
USER
S
1
LOAD
-1 =
USER
S
1
SAVE
-2 =
USER
S
2
LOAD
-3 =
USER
S
2
SAVE
-4 =
OR
SET
LOAD
With
USER
S
1
SAVE
and
USER
S
2
SAVE
, it is possible to save two different
parameter sets into the drive permanent memory for later use. Each set
contains parameter settings, including
, and
the results of the motor identification run. With
USER
S
1
LOAD
and
USER
S
2
LOAD
the sets can be taken back in use.
The automatic saving and loading of the override parameter set is
defined by
OR
SET
LOAD
, it can be loaded
manually.
9904
MOTOR CTRL MODE
1=SPEED,
3=SCALAR
Selects the motor control mode.
1 =
VECTOR
:
SPEED
– sensorless vector control mode
• Reference 1 is speed reference in rpm.
• Reference 2 is speed reference in % (100% is absolute maximum
speed, equal to the value of parameter 2002
MAXIMUM
SPEED
, or
2001
MINIMUM
SPEED
if the absolute value of the minimum speed is
greater than the maximum speed).
3 =
SCALAR
:
FREQ
– scalar control mode
• Reference 1 is frequency reference in Hz.
• Reference 2 is frequency reference in % (100% is absolute
maximum frequency, equal to the value of parameter 2008
MAXIMUM
FREQUENCY
, or 2007
MINIMUM
FREQUENCY
if the absolute value of the
minimum speed is greater than the maximum speed).
0 =
ENGLISH
1 =
ENGLISH
(
AM
) 2 =
DEUTSCH
3 =
ITALIANO
4 =
ESPAÑOL
5 =
PORTUGUES
6 =
NEDERLANDS
7 =
FRANCAIS
8 =
DANSK
9 =
SUOMI
10 =
SVENSKA
11 =
RUSSKI
12 =
POLSKI
13 =
TÜRKÇE
14 =
CZECH
Summary of Contents for ACH550-01
Page 1: ...ACH550 User s Manual ACH550 01 Drives 0 75 110 kW ACH550 UH Drives 1 150 HP ABB ...
Page 10: ...Update Notice 8 ...
Page 12: ......
Page 18: ...6 ACH550 User s Manual ...
Page 50: ...38 Preparing for installation ACH550 User s Manual ...
Page 325: ...313 ACH550 User s Manual ...
Page 358: ...346 ACH550 User s Manual ...
Page 409: ...Technical data 397 ACH550 User s Manual Frame size R1 IP54 UL Type 12 ...
Page 410: ...398 Technical data ACH550 User s Manual Frame size R2 IP54 UL Type 12 ...
Page 411: ...Technical data 399 ACH550 User s Manual Frame size R3 IP54 UL Type 12 ...
Page 412: ...400 Technical data ACH550 User s Manual Frame size R4 IP54 UL Type 12 ...
Page 413: ...Technical data 401 ACH550 User s Manual Frame size R5 IP54 UL Type 12 ...
Page 414: ...402 Technical data ACH550 User s Manual Frame size R6 IP54 UL Type 12 ...
Page 415: ...Technical data 403 ACH550 User s Manual Frame size R1 IP21 UL Type 1 ...
Page 416: ...404 Technical data ACH550 User s Manual Frame size R2 IP21 UL Type 1 ...
Page 417: ...Technical data 405 ACH550 User s Manual Frame size R3 IP21 UL Type 1 ...
Page 418: ...406 Technical data ACH550 User s Manual Frame size R4 IP21 UL Type 1 ...
Page 419: ...Technical data 407 ACH550 User s Manual Frame size R5 IP21 UL Type 1 ...
Page 420: ...408 Technical data ACH550 User s Manual Frame size R6 IP21 UL Type 1 ...
Page 453: ......