186
Parameter listing and descriptions
ACH550 User's Manual
1103
REF1 SELECT
0…17
Selects the signal source for external reference
REF
1.
0 =
KEYPAD
– Defines the control panel as the reference source.
1 =
AI
1 – Defines analog input 1 (
AI
1) as the reference source.
2 =
AI
2 – Defines analog input 2 (
AI
2) as the reference source.
3 =
AI
1/
JOYST
– Defines analog input 1 (
AI
1), configured for joystick
operation, as the reference source.
• The minimum input signal runs the drive at the maximum reference
in the reverse direction. Define the minimum using parameter 1104.
• The maximum input signal runs the drive at maximum reference in
the forward direction. Define the maximum using parameter 1105.
• Requires parameter 1003 = 3 (
REQUEST
).
WARNING!
Because the low end of the reference range commands full
reverse operation, do not use 0 V as the lower end of the reference
range. Doing so means that if the control signal is lost (which is a 0 V
input), the result is full reverse operation. Instead, use the following set-
up so that loss of the analog input triggers a fault, stopping the drive:
• Set parameter 1301
MINIMUM
AI
1 (1304
MINIMUM
AI
2) at 20% (2 V or
4 mA).
• Set parameter 3021
AI
1
FAULT
LIMIT
to a value 5% or higher.
• Set parameter 3001
AI
<
MIN
FUNCTION
to 1 (
FAULT
).
Code Description
Range
+2 %
-2 %
10 V /
Hysteresis 4 % of full scale
EXT
REF
1
MIN
-
EXT
REF
1
MIN
-
EXT
REF
1
MAX
EXT
REF
1
MIN
EXT
REF
1
MAX
-
EXT
REF
1
MIN
2 V / 4 mA
0 V / 0 mA
20 mA
Summary of Contents for ACH550-01
Page 1: ...ACH550 User s Manual ACH550 01 Drives 0 75 110 kW ACH550 UH Drives 1 150 HP ABB ...
Page 10: ...Update Notice 8 ...
Page 12: ......
Page 18: ...6 ACH550 User s Manual ...
Page 50: ...38 Preparing for installation ACH550 User s Manual ...
Page 325: ...313 ACH550 User s Manual ...
Page 358: ...346 ACH550 User s Manual ...
Page 409: ...Technical data 397 ACH550 User s Manual Frame size R1 IP54 UL Type 12 ...
Page 410: ...398 Technical data ACH550 User s Manual Frame size R2 IP54 UL Type 12 ...
Page 411: ...Technical data 399 ACH550 User s Manual Frame size R3 IP54 UL Type 12 ...
Page 412: ...400 Technical data ACH550 User s Manual Frame size R4 IP54 UL Type 12 ...
Page 413: ...Technical data 401 ACH550 User s Manual Frame size R5 IP54 UL Type 12 ...
Page 414: ...402 Technical data ACH550 User s Manual Frame size R6 IP54 UL Type 12 ...
Page 415: ...Technical data 403 ACH550 User s Manual Frame size R1 IP21 UL Type 1 ...
Page 416: ...404 Technical data ACH550 User s Manual Frame size R2 IP21 UL Type 1 ...
Page 417: ...Technical data 405 ACH550 User s Manual Frame size R3 IP21 UL Type 1 ...
Page 418: ...406 Technical data ACH550 User s Manual Frame size R4 IP21 UL Type 1 ...
Page 419: ...Technical data 407 ACH550 User s Manual Frame size R5 IP21 UL Type 1 ...
Page 420: ...408 Technical data ACH550 User s Manual Frame size R6 IP21 UL Type 1 ...
Page 453: ......