Parameter listing and descriptions
257
ACH550 User's Manual
5 =
THERMISTOR
(0) – Sensor configuration uses a thermistor.
• Motor thermal protection is activated through a digital input. Connect
a normally closed thermistor relay to a digital input. The drive reads
the digital input states as shown in the above table.
• When the digital input is ‘0’ the motor is overheated.
• See the figure in the introduction to this group.
6 =
THERMISTOR
(1) – Sensor configuration uses a thermistor.
• Motor thermal protection is activated through a digital input. Connect
a normally open thermistor relay to a digital input. The drive reads
the digital input states as shown in the above table.
• When the digital input is ‘1’ the motor is overheated.
• See the figure in the introduction to this group.
3502
INPUT SELECTION
1…8
Defines the input used for the temperature sensor.
1 =
AI
1 – PT100 and PTC
2 =
AI
2 – PT100 and PTC
3…8 =
DI
1…
DI
6 – Thermistor.
3503
ALARM LIMIT
-10…200ºC /
Defines the alarm limit for
0…5000 ohm
the motor temperature measurement.
• At motor temperatures above this limit, the drive displays an alarm
(2010,
MOTOR
OVERTEMP
)
For thermistors:
0 = De-activated.
1 = Activated.
3504
FAULT LIMIT
0…1
Defines the fault limit for the motor temperature measurement.
• At motor temperatures above this limit, the drive displays a fault (9,
MOT
OVERTEMP
) and stops the drive.
For thermistors:
0 = De-activated.
1 = Activated.
Code Description
Range
Summary of Contents for ACH550-01
Page 1: ...ACH550 User s Manual ACH550 01 Drives 0 75 110 kW ACH550 UH Drives 1 150 HP ABB ...
Page 10: ...Update Notice 8 ...
Page 12: ......
Page 18: ...6 ACH550 User s Manual ...
Page 50: ...38 Preparing for installation ACH550 User s Manual ...
Page 325: ...313 ACH550 User s Manual ...
Page 358: ...346 ACH550 User s Manual ...
Page 409: ...Technical data 397 ACH550 User s Manual Frame size R1 IP54 UL Type 12 ...
Page 410: ...398 Technical data ACH550 User s Manual Frame size R2 IP54 UL Type 12 ...
Page 411: ...Technical data 399 ACH550 User s Manual Frame size R3 IP54 UL Type 12 ...
Page 412: ...400 Technical data ACH550 User s Manual Frame size R4 IP54 UL Type 12 ...
Page 413: ...Technical data 401 ACH550 User s Manual Frame size R5 IP54 UL Type 12 ...
Page 414: ...402 Technical data ACH550 User s Manual Frame size R6 IP54 UL Type 12 ...
Page 415: ...Technical data 403 ACH550 User s Manual Frame size R1 IP21 UL Type 1 ...
Page 416: ...404 Technical data ACH550 User s Manual Frame size R2 IP21 UL Type 1 ...
Page 417: ...Technical data 405 ACH550 User s Manual Frame size R3 IP21 UL Type 1 ...
Page 418: ...406 Technical data ACH550 User s Manual Frame size R4 IP21 UL Type 1 ...
Page 419: ...Technical data 407 ACH550 User s Manual Frame size R5 IP21 UL Type 1 ...
Page 420: ...408 Technical data ACH550 User s Manual Frame size R6 IP21 UL Type 1 ...
Page 453: ......