Diagnostics and maintenance
353
ACH550 User's Manual
21
CURR
MEAS
Internal fault. Current measurement is out of
range. Contact your local ABB
representative.
22
SUPPLY
PHASE
Ripple voltage in the DC link is too high.
Check for and correct:
• missing mains phase
• blown fuse.
23
RESERVED
Not used.
24
OVERSPEED
Motor speed is greater than 120% of the
larger (in magnitude) of 2001
MINIMUM
SPEED
or 2002
MAXIMUM
SPEED
. Check for and
correct:
• parameter settings for 2001 and 2002
• adequacy of motor braking torque
• applicability of torque control
• brake chopper and resistor.
25
RESERVED
Not used.
26
DRIVE
ID
Internal fault. Configuration block drive ID is
not valid.
27
CONFIG
FILE
Internal configuration file has an error.
Contact your local ABB representative.
28
SERIAL
1
ERR
Fieldbus communication has timed out.
Check for and correct:
• fault setup (3018
COMM
FAULT
FUNC
and
3019
COMM
FAULT
TIME
)
• communication settings (
as appropriate)
• poor connections and/or noise on line.
29
EFB
CON
FILE
Error in reading the configuration file for the
fieldbus adapter.
30
FORCE
TRIP
Fault trip forced by the fieldbus. See the
fieldbus user’s manual.
Fault
code
Fault name in
the panel
Description and
recommended corrective action
Summary of Contents for ACH550-01
Page 1: ...ACH550 User s Manual ACH550 01 Drives 0 75 110 kW ACH550 UH Drives 1 150 HP ABB ...
Page 10: ...Update Notice 8 ...
Page 12: ......
Page 18: ...6 ACH550 User s Manual ...
Page 50: ...38 Preparing for installation ACH550 User s Manual ...
Page 325: ...313 ACH550 User s Manual ...
Page 358: ...346 ACH550 User s Manual ...
Page 409: ...Technical data 397 ACH550 User s Manual Frame size R1 IP54 UL Type 12 ...
Page 410: ...398 Technical data ACH550 User s Manual Frame size R2 IP54 UL Type 12 ...
Page 411: ...Technical data 399 ACH550 User s Manual Frame size R3 IP54 UL Type 12 ...
Page 412: ...400 Technical data ACH550 User s Manual Frame size R4 IP54 UL Type 12 ...
Page 413: ...Technical data 401 ACH550 User s Manual Frame size R5 IP54 UL Type 12 ...
Page 414: ...402 Technical data ACH550 User s Manual Frame size R6 IP54 UL Type 12 ...
Page 415: ...Technical data 403 ACH550 User s Manual Frame size R1 IP21 UL Type 1 ...
Page 416: ...404 Technical data ACH550 User s Manual Frame size R2 IP21 UL Type 1 ...
Page 417: ...Technical data 405 ACH550 User s Manual Frame size R3 IP21 UL Type 1 ...
Page 418: ...406 Technical data ACH550 User s Manual Frame size R4 IP21 UL Type 1 ...
Page 419: ...Technical data 407 ACH550 User s Manual Frame size R5 IP21 UL Type 1 ...
Page 420: ...408 Technical data ACH550 User s Manual Frame size R6 IP21 UL Type 1 ...
Page 453: ......