136
Serial communications
ACH550 User's Manual
The new settings will take effect when the drive is next powered
up, or when parameter 5127 is activated.
Drive control parameters
After the fieldbus communication has been set up, the drive
control parameters listed in the tables below should be checked
and adjusted where necessary.
The “Setting for fieldbus control & description” column gives the
value to use when the fieldbus interface is the desired source or
destination for that particular signal as well as a description of
the parameter.
The fieldbus signal routes and message composition are
explained later in section
5131
FBA STATUS
0…6
Contains the status of the adapter module.
0 =
IDLE
– Adapter not configured.
1 =
EXEC
.
INIT
– Adapter is initializing.
2 =
TIME
OUT
– A time-out has occurred in the communication between
the adapter and the drive.
3 =
CONFIG
ERROR
– Adapter configuration error.
• The major or minor revision code of the adapter’s CPI firmware
revision differs from that stated in the drive’s configuration file.
4 =
OFF
-
LINE
– Adapter is off-line.
5 =
ON
-
LINE
– Adapter is on-line.
6 =
RESET
– Adapter is performing a hardware reset.
5132
FBA CPI FW REV
0…0xFFFF
Contains the revision of the module’s CPI program. Format is xyz,
where:
• x = major revision number
• y = minor revision number
• z = correction number.
Example:
107 = revision 1.07
5133
FBA APPL FW REV
0…0xFFFF
Contains the revision of the module’s application program. Format is
xyz, where:
• x = major revision number
• y = minor revision number
• z = correction number.
Example:
107 = revision 1.07
Code Description
Range
Summary of Contents for ACH550-01
Page 1: ...ACH550 User s Manual ACH550 01 Drives 0 75 110 kW ACH550 UH Drives 1 150 HP ABB ...
Page 10: ...Update Notice 8 ...
Page 12: ......
Page 18: ...6 ACH550 User s Manual ...
Page 50: ...38 Preparing for installation ACH550 User s Manual ...
Page 325: ...313 ACH550 User s Manual ...
Page 358: ...346 ACH550 User s Manual ...
Page 409: ...Technical data 397 ACH550 User s Manual Frame size R1 IP54 UL Type 12 ...
Page 410: ...398 Technical data ACH550 User s Manual Frame size R2 IP54 UL Type 12 ...
Page 411: ...Technical data 399 ACH550 User s Manual Frame size R3 IP54 UL Type 12 ...
Page 412: ...400 Technical data ACH550 User s Manual Frame size R4 IP54 UL Type 12 ...
Page 413: ...Technical data 401 ACH550 User s Manual Frame size R5 IP54 UL Type 12 ...
Page 414: ...402 Technical data ACH550 User s Manual Frame size R6 IP54 UL Type 12 ...
Page 415: ...Technical data 403 ACH550 User s Manual Frame size R1 IP21 UL Type 1 ...
Page 416: ...404 Technical data ACH550 User s Manual Frame size R2 IP21 UL Type 1 ...
Page 417: ...Technical data 405 ACH550 User s Manual Frame size R3 IP21 UL Type 1 ...
Page 418: ...406 Technical data ACH550 User s Manual Frame size R4 IP21 UL Type 1 ...
Page 419: ...Technical data 407 ACH550 User s Manual Frame size R5 IP21 UL Type 1 ...
Page 420: ...408 Technical data ACH550 User s Manual Frame size R6 IP21 UL Type 1 ...
Page 453: ......