1-108
ACH550-UH User’s Manual
Parameters
Group 16: SYSTEM CONTROLS
This group defines a variety of system level locks, resets and enables.
Group 16: System Controls
Code Description Range
Resolution
Default
S
1601
RUN ENABLE
-6…7
1
0 (
NOT
SEL
)
Selects the source of the run enable signal.
0 =
NOT
SEL
– Allows the drive to start without an external run enable signal.
1 =
DI
1 – Defines digital input
DI
1 as the run enable signal.
• This digital input must be activated for run enable.
• If the voltage drops and de-activates this digital input, the drive will coast to stop and not start until the run enable
signal resumes.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the run enable signal.
• See
DI
1 above.
7 =
COMM
– Assigns the fieldbus Command Word as the source for the run enable signal.
• Bit 6 of the Command Word 1 (parameter 0301) activates the run disable signal.
• See fieldbus user’s manual for detailed instructions.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the run enable signal.
• This digital input must be de-activated for run enable.
• If this digital input activates, the drive will coast to stop and not start until the run enable signal resumes.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the run enable signal.
• See
DI
1(
INV
) above.
1602
PARAMETER LOCK
0…2
1
1 (
OPEN
)
Determines if the control panel can change parameter values.
• This lock does not limit parameter changes made by macros.
• This lock does not limit parameter changes written by fieldbus inputs.
• This parameter value can be changed only if the correct pass code is entered. See parameter 1603
PASS
CODE
.
0 =
LOCKED
– You cannot use the control panel to change parameter values.
• The lock can be opened by entering the valid pass code to parameter 1603.
1 =
OPEN
– You can use the control panel to change parameter values.
2 =
NOT
SAVED
– You can use the control panel to change parameter values, but they are not stored in permanent
memory.
• Set parameter 1607
PARAM
SAVE
to 1 (
SAVE
...) to store changed parameter values to memory.
1603
PASS CODE
0…65535
1
0
Entering the correct pass code allows you to change the parameter lock.
• See parameter 1602 above.
• The code 358 allows you to change the value of the parameter 1602 once.
• This entry reverts back to 0 automatically.
1604
FAULT RESET SEL
-6…8
1
0 (
KEYPAD
)
Selects the source for the fault reset signal. The signal resets the drive after a fault trip if the cause of the fault no
longer exists.
0 =
KEYPAD
– Defines the control panel as the only fault reset source.
• Fault reset is always possible with control panel.
1 =
DI
1 – Defines digital input
DI
1 as a fault reset source.
• Activating the digital input resets the drive.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as a fault reset source.
• See
DI
1 above.
7 =
START
/
STOP
– Defines the Stop command as a fault reset source.
• Do not use this option when fieldbus communication provides the start, stop and direction commands.
8 =
COMM
– Defines the fieldbus as a fault reset source.
• The Command Word is supplied through fieldbus communication.
• The bit 4 of the Command Word 1 (parameter 0301) resets the drive.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as a fault reset source.
• De-activating the digital input resets the drive.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as a fault reset source.
• See
DI
1(
INV
) above.
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......