1-116
ACH550-UH User’s Manual
Parameters
2007
MINIMUM FREQ
-500.0…500.0 Hz
0.1 Hz
0.0 Hz
Defines the minimum limit for the drive output frequency.
• A positive or zero minimum frequency value defines two ranges,
one positive and one negative.
• A negative minimum frequency value defines one speed range.
See the figure.
Note:
Keep
MINIMUM
FREQ
MAXIMUM
FREQ
.
2008
MAXIMUM FREQ
0.0…500.0 Hz
0.1 Hz
60.0 Hz (US)
Defines the maximum limit for the drive output frequency.
2013
MIN TORQUE SEL
-6…7
1
0 (
MIN
TORQUE
1)
Defines control of the selection between two minimum torque limits (2015
MIN
TORQUE
1 and 2016
MIN
TORQUE
2).
0 =
MIN
TORQUE
1 – Selects 2015
MIN
TORQUE
1 as the minimum limit used.
1 =
DI
1 – Defines digital input
DI
1 as the control for selecting the minimum limit used.
• Activating the digital input selects
MIN
TORQUE
2 value.
• De-activating the digital input selects
MIN
TORQUE
1 value.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for selecting the minimum limit used.
• See
DI
1 above.
7 =
COMM
– Defines bit 15 of the Command Word 1 as the control for selecting the minimum limit used.
• The Command Word is supplied through fieldbus communication.
• The Command Word is parameter 0301.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for selecting the minimum limit used.
• Activating the digital input selects
MIN
TORQUE
1 value.
• De-activating the digital input selects
MIN
TORQUE
2 value.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for selecting the minimum limit
used.
• See
DI
1(
INV
) above.
2014
MAX TORQUE SEL
-6…7
1
0 (
MAX
TORQUE
1)
Defines control of the selection between two maximum torque limits (2017
MAX
TORQUE
1 and 2018
MAX
TORQUE
2).
0 =
MAX
TORQUE
1 – Selects 2017
MAX
TORQUE
1 as the maximum limit used.
1 =
DI
1 – Defines digital input
DI
1 as the control for selecting the maximum limit used.
• Activating the digital input selects
MAX
TORQUE
2 value.
• De-activating the digital input selects
MAX
TORQUE
1 value.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for selecting the maximum limit used.
• See
DI
1 above.
7 =
COMM
– Defines bit 15 of the Command Word 1 as the control for selecting the maximum limit used.
• The Command Word is supplied through fieldbus communication.
• The Command Word is parameter 0301.
-1 =
DI
1(
INV
) – Defines an inverted digital input di1 as the control for selecting the maximum limit used.
• Activating the digital input selects
MAX
TORQUE
1 value.
• De-activating the digital input selects
MAX
TORQUE
2 value.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for selecting the maximum limit
used.
• See
DI
1(
INV
) above.
Group 20: Limits
Code Description Range
Resolution
Default
S
P 2007
P 2008
Freq
-(P 2007)
-(P 2008)
P 2008
P 2007
Frequency range allowed
Frequency range allowed
Frequency range allowed
Time
Freq
Time
2007 value is > 0
0
0
2007 value is < 0
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......