ACH550-UH User’s Manual
1-153
Parameters
4007
UNIT SCALE
0…4
1
1
Defines the decimal point location in PID controller actual values.
• Enter the decimal point location counting in from the right end of the
entry.
• See the table for an example using pi (3.14159).
4008
0% VALUE
Depends on Units
-
0.0%
and Scale
Defines (together with the next parameter) the scaling applied to the
PID controller’s actual values (PID1 parameters 0128, 0130 and
0132).
• Units and scale are defined by parameters 4006 and 4007.
4009
100% VALUE
Depends on Units
-
100.0%
and Scale
Defines (together with the previous parameter) the scaling applied to the PID controller’s actual values.
• Units and scale are defined by parameters 4006 and 4007. See parameter 4008.
Group 40: Process PID Set 1
Code Description Range
Resolution
Default
S
4007 value
Entry
Display
0
00003
3
1
00031
3.1
2
00314
3.14
3
03142
3.142
4
31416
3.1416
Internal scale (%)
P 4009
P 4008
100%
0%
Units (P4006)
Scale (P4007)
-1000.0%
+1000.0%
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......