1-160
ACH550-UH User’s Manual
Parameters
Group 42: EXT / TRIM PID
This group defines the parameters used for the second PID controller (PID2), which
is used for the External / Trimming PID.
The operation of parameters 4201
…
4221 is analogous with Process PID set 1
(PID1) parameters 4001…4021.
Group 42: Ext / Trim PID
Code Description Range
Resolution
Default
S
4201
…
4221
See 4001 …4021
Note:
The Default value for parameter 4201 is 1.0.
The Default value for parameter 4202 is 60.0 s.
The Default value for parameter 4210 is 1 (
AI
1).
4228
ACTIVATE
-6…12
-
0 (
NOT
SEL
)
Defines the source for enabling the external PID function.
• Requires 4230
TRIM
MODE
= 0 (
NOT
SEL
).
0 =
NOT
SEL
– Disables external PID control.
1 =
DI
1 – Defines digital input
DI
1 as the control for enabling external PID control.
• Activating the digital input enables external PID control.
• De-activating the digital input disables external PID control.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for enabling external PID control.
• See
DI
1 above.
7 =
DRIVE
RUN
– Defines the start command as the control for enabling external PID control.
• Activating the start command (drive is running) enables external PID control.
8 =
ON
– Defines the power-on as the control for enabling external PID control.
• Activating power to the drive enables external PID control.
9…12 =
TIMED
FUNC
1…4 – Defines the Timed function as the control for enabling external PID control (Timed
function active enables external PID control).
• See
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for enabling external PID control.
• Activating the digital input disables external PID control.
• De-activating the digital input enables external PID control.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for enabling external PID
control.
• See
DI
1(
INV
) above.
4229
OFFSET
0.0…100.0%
0.1%
0.0%
Defines the offset for the PID output.
• When PID is activated, output starts from this value.
• When PID is deactivated, output resets to this value.
• Parameter is active when 4230
TRIM
MODE
= 0 (trim mode is not active).
4230
TRIM MODE
0…2
1
0 (
NOT
SEL
)
Selects the type of trim, if any. Using the trim it is possible to combine a corrective factor to the drive reference.
0 =
NOT
SEL
– Disables the trim function.
1 =
PROPORTIONAL
– Adds a trim factor that is proportional to the rpm/Hz reference.
2 =
DIRECT
– Adds a trim factor based on the control loop’s maximum limit.
4231
TRIM SCALE
-100.0%…100.0%
0.1%
0.0%
Defines the multiplier (as a percent, plus or minus) used in the trim mode.
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......