ACH550-UH User’s Manual
1-299
Technical data
Ratings, 500…600 volt drives
Abbreviated column headers are described in
below.
Symbols
Sizing
The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current.
Note 1:
The ratings apply in ambient temperature of 40 °C (104 °F).
Type Code
Normal Use
Frame Size
ACH550-xx-
see below
I
2n
A
P
n
HP
Three-phase supply voltage,
500
…
600 V
-02A7-6
2.7
2
R2
-03A9-6
3.9
3
R2
-06A1-6
6.1
5
R2
-09A0-6
9
7.5
R2
-011A-6
11
10
R2
-017A-6
17
15
R2
-022A-6
22
20
R3
-027A-6
27
25
R3
-032A-6
32
30
R4
-041A-6
41
40
R4
-052A-6
52
50
R4
-062A-6
62
60
R4
-077A-6
77
75
R6
-099A-6
99
100
R6
-125A-6
125
125
R6
-144A-6
144
150
R6
Typical ratings:
Normal use
(10% overload capability)
I
2n
continuous rms current. 10% overload is allowed for one minute in ten minutes.
P
n
typical motor power in normal use. The kilowatt power ratings apply to most IEC, 4-pole
motors. The Horsepower ratings apply to most 4-pole NEMA motors.
1 min.
I
n
1,1x
I
n
9 min.
1 min.
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......