2-26
ACH550 E-Clipse Bypass User’s Manual
Installation
5. On the E-Clipse Bypass control panel, either the
Drive Selected
or
Bypass Selected
LED should be illuminated. Pressing the
Drive Select
or
Bypass Select
key should
switch the bypass back and forth between the
Drive
mode and the
Bypass
mode as
indicated by the LEDs above each button. Check that the bypass control panel
switches the system between modes. Leave the system in the Bypass mode when
proceeding to the next step.
6. Check to see that pressing the:
•
Auto
key on the bypass control panel causes the bottom line on the E-Clipse
Bypass display to indicate “
Bypass in Auto
”
• Hand key on the bypass control panel generates a Motor Phase Fault.
• Under normal conditions (motor connected) pressing the Hand key on the bypass
control panel causes the bottom line on the E-Clipse Bypass display to indicate
“Hand #A Run”
• OFF key on the bypass control panel causes the bottom line on the E-Clipse
Bypass display to indicate “Off Stop”
7. For Steps 8 through 14, ACH550 Drive Parameter 9904 must be set to “Scalar:
Freq”. After successful completion of Step 13, Parameter 9904 may be set to
“Vector: Speed” if very specific application requirements make it necessary to use
this type of motor control. Operation using the “Vector: Speed” setting is
unnecessary for control of almost all fan and pump applications. Refer to the
ACH550-UH User’s Manual on page
for details on setting parameters.
8. Press the
Drive Select
key on the E-Clipse Bypass control panel. The
Drive Select
LED should be illuminated.
9. Check to see that pressing the:
•
Auto
key on the bypass control panel causes the E-Clipse Bypass display to
indicate “
Bypass in Auto
”
•
Hand
key on the bypass control panel causes no change to the E-Clipse Bypass
display
•
OFF
key on the bypass control panel causes the E-Clipse Bypass display to
indicate “
Bypass in Off”
10. Press the
HAND
key on the drive control panel. Note that the top line of the control
panel display indicates “HAND” and run as a clockwise rotating arrow. The
Drive
Run
LED on the E-Clipse Bypass control panel should be illuminated.
11. Press the
UP
arrow on the drive control panel. Note that the speed reference
indication in the top line of the drive control panel display increases from “0.0% SP.”
12. In the middle line of the drive control panel display, the output current indication
should indicate “0.0 A.”
13. Press the
DOWN
arrow on the drive control panel until the speed and frequency
indications return to “0.0.”
14. Press the
OFF
key on the drive control panel. Note that the bottom line of the drive
contol panel display indicates “Off.”
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......