ACH550 E-Clipse Bypass User’s Manual
2-47
Bypass functions overview
Bypass No Fault (7) [BYP NOT FLT]
If configured for
Bypass No Fault,
the relay is energized during normal operation.
The
Bypass No Fault
relay is de-energized when power is removed from the system,
a bypass fault has occurred or when the bypass motor overload/underload
protection has tripped. The specific nature of the fault is indicated on the bypass
control panel display.
Bypass Alarm (8) [BYPASS ALRM]
If configured for
Bypass Alarm,
the relay is energized when a bypass alarm is
present. The specific nature of the alarm is indicated on the bypass control panel
display. The
Bypass Alarm
relay is de-energized during normal operation.
Drive Fault (9) [DRIVE FAULT]
If configured for
Drive Fault,
the relay is energized when a drive fault has occurred.
The specific nature of the fault is indicated on the drive control panel display. The
Drive Fault
relay is de-energized during normal control panel.
Drive No Fault (10) [DRV NOT FLT]
If configured for
Drive No Fault
, the relay is energized during normal operation. The
Drive No Fault
relay is de-energized when power is removed from the system, or
when a drive fault has occurred. The specific nature of the fault is indicated on the
drive control panel display.
Drive Alarm (11) [DRIVE ALARM]
If configured for
Drive Alarm,
the relay is energized when a drive alarm is present.
The specific nature of the alarm is indicated on the drive control panel display. The
Drive Alarm
relay is de-energized during normal operation.
Override (12) [OVERRIDE]
If configured for
Override
, the relay is energized when Smoke Control Override or
Advanced Override mode is selected and de-energized in all other modes. The
Override
relay is de-energized during normal operation.
Bypass Hand (13) [BYPASS HAND]
If configured for
Bypass Hand
, the relay is energized when the motor is running in
Bypass Mode and Hand (manual operation) is selected. The
Bypass Hand
relay is
de-energized when Bypass Auto or Bypass Off are selected.
Bypass Off (14) [BYPASS OFF]
If configured for
Bypass Off
, the relay is energized when the bypass control mode
Off
is selected. The
Bypass Off
relay is de-energized when either Bypass Auto or
Bypass Hand are selected.
Bypass Auto (15) [BYPASS AUTO]
If configured for
Bypass Auto,
the relay is energized when the bypass control mode
Auto
is selected. The
Bypass Auto
relay is de-energized when either Bypass Off or
Bypass Hand are selected.
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......