2-124
ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
FLN protocol technical data – system
System overview
The FLN fieldbus connection to the E-Clipse Bypass system is based on an industry
standard RS-485 physical interface. The FLN (Floor Level Network) Fieldbus
protocol is a serial communication protocol, used by the Siemens APOGEE®
system. The system interface is specified in Siemens application 2734.
Supported features
The system supports all required FLN features.
When bypass parameter 1625 COMM CTL = (0) DRIVE ONLY, the drive’s FLN
points are all supported using the drive’s device address. The bypass’s FLN points
related to the control word are no longer valid.
Bypass FLN points not valid
When bypass parameter 1625 COMM CTL = (1) SYSTEM, the drive’s FLN following
objects related to control are no longer available when using the drive’s device
address.
Drive FLN objects not valid
Point #
Name
24
RUN.STOP CMD
26
OVERRIDE CMD
35
RUN ENA CMD
50
START ENA 1
51
START ENA 2
52
START ENA 3
53
START ENA 4
94
RESET FAULT
Point #
Name
24
RUN.STOP CMD
35
ENA DIS CMD
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......