ACH550 E-Clipse Bypass User’s Manual
Embedded fieldbus
37
FLN CTL SRC
Indicates if FLN is a source for control inputs
(1 = YES, 0 = NO).
Note that this status point is true if any of the following control
inputs are from FLN: Run/Stop, Ext1/2 Select or Run Enable.
38
FLN REF1 SRC
Indicates if FLN is the source for speed reference 1
(1 = YES, 0 = NO).
39
FLN REF2 SRC
Indicates if FLN is the source for speed reference 2
(1 = YES, 0 = NO).
40
RO1 COMMAND Controls the output state of Relay 1.
Parameter 1401 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 0
41
RO2 COMMAND Controls the output state of Relay 2.
Parameter 1402 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 1
42
RO3 COMMAND Controls the output state of Relay 3.
Parameter 1403 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 2
43
RO4 COMMAND Controls the output state of Relay 4. Access to relay 4 require
ACH550 option OREL.
Parameter 1410 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 3
44
RO5 COMMAND Controls the output state of Relay 5. Access to relay 5 require
ACH550 option OREL.
Parameter 1411 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 4
45
RO6 COMMAND Controls the output state of Relay 6. Access to relay 6 require
ACH550 option OREL.
Parameter 1412 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 5
46
AO1 COMMAND Controls Analog Output 1.
Parameter 1501 must be set to this value for FLN to have this
control.
0135
(COMM
VALUE 1)
47
AO2 COMMAND Controls Analog Output 2.
Parameter 1507 must be set to this value for FLN to have this
control.
0136
(COMM
VALUE 2)
48
RESET RUN
TIME
Commanded by FLN to reset the cumulative run timer (1 =
RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
49
RESET KWH
Commanded by FLN to reset the cumulative kilowatt-hour
counter (1 = RESET, 0 = NO).
The control input is rising-edge sensitive, so, once the
command is issued, this point automatically returns to its
inactive state. This “momentary” operation avoids any need
for an explicit command to clear the point before a
subsequent reset can be issued.
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
Summary of Contents for ACH550-BCR
Page 4: ...iv Manual contents ...
Page 6: ......
Page 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Page 36: ...1 32 ACH550 UH User s Manual Installation ...
Page 70: ...1 66 ACH550 UH User s Manual Application macros ...
Page 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Page 348: ......
Page 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Page 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Page 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Page 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Page 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Page 608: ......
Page 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Page 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Page 641: ......